AI Cable Size Assistant
Enter the circuit current, supply voltage, one-way cable run, your maximum acceptable voltage drop (3% is typical for branch circuits) and the conductor material. The assistant computes the minimum cross-section from the voltage-drop limit and rounds up to the nearest standard size. It deliberately does NOT declare the result code-compliant: ampacity, insulation type, installation method, grouping and derating must be verified against IEC 60364 / NEC tables by a qualified professional.
Ask in plain words
The AI reads your question and fills in the parameters; a verified calculator engine does every calculation.
How to use the AI Cable Size Assistant
- Enter the circuit current (from the load or breaker rating) and system voltage.
- Enter the one-way cable length and your voltage-drop limit.
- Pick copper or aluminum — resistivity differs by ~60%.
- Press Calculate for the minimum cross-section, then verify ampacity and installation conditions against your local code.
How the calculation works
Voltage drop: single-phase/DC ΔU = 2·L·I·ρ ÷ A; three-phase ΔU = √3·L·I·ρ ÷ A, with ρ_copper = 0.0175 Ω·mm²/m and ρ_aluminum = 0.0283 Ω·mm²/m (conductor operating temperature ≈ 20–40 °C). Required A ≥ 2·L·I·ρ ÷ (V·maxDrop%), rounded up to the standard series 1.5–240 mm². ⚠ Preliminary only: final selection must satisfy ampacity/derating/protective-device coordination per the applicable standard.
Example questions
- “20 A at 230 V, 25 m run, copper, max 3% drop”
- “Solar panel to battery 12 A at 12 V, 8 m, 2% drop, copper”
- “Submersible pump 9 A, 120 m from the panel, aluminum, 5%”
Related calculators
Prefer doing it yourself? These dedicated calculators run the same verified formulas.