The formula behind it
W = VA × pf; VA = W ÷ pf; var = VA × sin(acos pf)- VA
- apparent power — what the wiring actually carries
- W
- real power — what does useful work
- var
- reactive power — the circulating component that does no work
The VA–W pair is the power triangle. Apparent power (VA) is what cables, transformers and UPS units must carry; real power (W) is what the load converts to work; their ratio is the power factor. A 1,000 VA UPS at pf 0.8 powers just 800 W of equipment — sizing on watts alone undersizes hardware. The reactive term completes the triangle: VA² = W² + var².
How to use this calculator
- 1
Choose the direction: VA→W (size a load) or W→VA (size a UPS or breaker).
- 2
Enter the power value and the power factor (nameplate or measured; 1.0 for resistive).
- 3
Press Calculate — real, apparent and reactive powers are shown together.
Worked examples
Server load
1,500 VA at pf 0.95 → 1,425 W real, 468 var reactive.
UPS choice
900 W of gear at pf 0.8 → 1,125 VA minimum rating.